Gateway ProfiNet/AS-i, 1 Master, P24
Product discontinued since 2023-02-13
| Art.No.: | 56470 |
| Weight: | 0.5 kg |
| Country of origin: | DE |
| Model designation: | Gateway PNIO/AS-i-24, 1 Master 3.0 IP20 |
Description
AS-Interface/PROFINET
Power 24V
Specification 3.0
Diagnostic via BUS
Current manuals, GSD/type data can be downloaded at: www.murrelektronik.com
Other gateways on request.
Gateway-Singlemaster
AS-Interface data decoupling integrated
AS-Interface duplicate address detection
AS-Interface EMC detector integrated
Power 24V
Specification 3.0
Diagnostic via BUS
Current manuals, GSD/type data can be downloaded at: www.murrelektronik.com
Other gateways on request.
Gateway-Singlemaster
AS-Interface data decoupling integrated
AS-Interface duplicate address detection
AS-Interface EMC detector integrated
Technical Data
Header
| Material short text | Gateway PNIO/AS-i-24, 1 Master 3.0 IP20 |
|---|
Electrical data
| Security level | PELV |
|---|---|
| Rated operating current AS-Interface max. | 250 mA |
Electrical data | Supply
| Operating voltage DC | 24 V |
|---|---|
| Operating voltage DC min. | 20 V |
| Operating voltage DC max. | 30.6 V |
Industrial communication
| Supported protocol | PROFINET |
|---|
Industrial communication | Bus data
| Automatic baudrate detection | no |
|---|---|
| Baud rate max. | 100 MBaud |
Industrial communication | AS-Interface
| AS-i specification | V3.0 |
|---|---|
| Number of slaves max. | 62 |
| Diagnostic interface serial | RJ45/Fieldbus |
| Cycle time AS-i | 150 µs × (number of slaves + 2) |
Industrial communication | Profinet
| PROFINET conformance class | B |
|---|
Installation | Connection
| Family construction form | RJ45 |
|---|
Device protection | Electrical
| Degree of protection (EN IEC 60529) | IP20 |
|---|---|
| Rated insulation voltage | 500 V |
Mechanical data | Mounting data
| Height | 120 mm |
|---|---|
| Width | 85 mm |
| Depth | 83 mm |
| Mounting method | geschnappt |
| Suitable for mounting type | (EN 60715), mounting rail |
Environmental characteristics | Electromagnetic compatibility
| Conducted interference emission (IEC 61000-6-4) | compliant |
|---|---|
| Immunitiy standard for industrial environments (IEC 61000-6-2) | compliant |
Environmental characteristics | Climatic
| Operating temperature min. | 0 °C |
|---|---|
| Operating temperature max. | 55 °C |
| Storage temperature min. | -25 °C |
| Storage temperature max. | 85 °C |
Conformity
| Product standard | IEC/EN 61131-2, EN/IEC 62026-2 |
|---|
Commercial data
| URL Webshop | https://shop.murrelektronik.com/56470 |
|---|---|
| GTIN | 4048879553872 |
| ECLASS-6.0 | 27242608 |
| ECLASS-6.1 | 27242608 |
| ECLASS-7.0 | 27242608 |
| ECLASS-8.0 | 27242608 |
| ECLASS-9.0 | 27242608 |
| ECLASS-10.1 | 27242608 |
| ECLASS-11.1 | 27242608 |
| ECLASS-12.0 | 27242608 |
| ETIM-5.0 | EC001604 |
| ETIM-6.0 | EC001604 |
| ETIM-7.0 | EC001604 |
| ETIM-8.0 | EC001604 |
| customs tariff number | 85176200 |
| EAN | 4048879553872 |
| Packaging unit | 1 |
Accessories
---- Programming Device ----